02 декабря 2020 27 апреля 2022 Всякое


DALI COMMANDS

Type of addresses:

address byte:

Short or group address

YAAAAAAS

Short addresses (64)

0AAAAAAS

Group addresses (16)

100AAAAS

Broadcast

100AAAAS

Special command

101CCCC1

Special command

110CCCC1

 

 

S: selector bit:

S = ‘0’ direct arc power level following

 

S = ‘1’ command following

 

Y = ‘0’ short address

 

Y = ‘1’ group address or broadcast

A: significant address bit

 

C: significant command bit

 

 

 

Table 1 contains a complete summary of the DALI command set. Basically there are four types of commands (forward frames):

1. Direct / Indirect arc power control commands – used to set ballast power level.

2. Configuration commands – configures the ballast (for example: add to a group or store level). Command must be repeated within 100 ms, otherwise it’s ignored.

3. Query commands – ask slave (ballast) for status information (for example: power level or version number). The slave can send a backward frame.

4. Special commands – used to initialize and setup the ballast, some must be repeated within 100 ms, and some require an answer from the slave. Most commands are only processed within 15 minutes after an “INITIALIZE” command is received.

Table 1. DALI Command Set Summary

Number

Command Code

Repeat < 100 ms

Answer Slave

Command Name

-

YAAA AAA0 XXXX XXXX

no

no

DIRECT ARC POWER CONTROL

0

YAAA AAA1 0000 0000

no

no

OFF

1

YAAA AAA1 0000 0001

no

no

UP

2

YAAA AAA1 0000 0010

no

no

DOWN

3

YAAA AAA1 0000 0011

no

no

STEP UP

4

YAAA AAA1 0000 0100

no

no

STEP DOWN

5

YAAA AAA1 0000 0101

no

no

RECALL MAX LEVEL

6

YAAA AAA1 0000 0110

no

no

RECALL MIN LEVEL

7

YAAA AAA1 0000 0111

no

no

STEP DOWN AND OFF

8

YAAA AAA1 0000 1000

no

no

ON AND STEP UP

9-15

YAAA AAA1 0000 1XXX

 

 

RESERVED

16 - 31

YAAA AAA1 0001 XXXX

no

no

GO TO SCENE

32

YAAA AAA1 0010 0000

yes

no

RESET

33

YAAA AAA1 0010 0001

yes

no

STORE ACTUAL LEVEL IN THE DTR

34 - 41

YAAA AAA1 0010 XXXX

 

 

RESERVED

42

YAAA AAA1 0010 1010

yes

no

STORE THE DTR AS MAX LEVEL

43

YAAA AAA1 0010 1011

yes

no

STORE THE DTR AS MIN LEVEL

44

YAAA AAA1 0010 1100

yes

no

STORE THE DTR AS SYSTEM FAILURE LEVEL

45

YAAA AAA1 0010 1101

yes

no

STORE THE DTR AS POWER ON LEVEL

46

YAAA AAA1 0010 1110

yes

no

STORE THE DTR AS FADE TIME

47

YAAA AAA1 0010 1111

yes

no

STORE THE DTR AS FADE RATE

48 - 63

YAAA AAA1 0011 XXXX

 

 

RESERVED

64 - 79

YAAA AAA1 0100 XXXX

yes

no

STORE THE DTR AS SCENE

80 - 95

YAAA AAA1 0101 XXXX

yes

no

REMOVE FROM SCENE

96 - 111

YAAA AAA1 0110 XXXX

yes

no

ADD TO GROUP

112 -127

YAAA AAA1 0111 XXXX

yes

no

REMOVE FROM GROUP

128

YAAA AAA1 1000 0000

yes

no

STORE DTR AS SHORT ADDRESS

129 -143

YAAA AAA1 1000 XXXX

 

 

STORE DTR AS SHORT ADDRESS

144

YAAA AAA1 1001 0000

no

yes

QUERY STATUS

145

YAAA AAA1 1001 0001

no

yes

QUERY BALLAST

146

YAAA AAA1 1001 0010

no

yes

QUERY LAMP FAILURE

147

YAAA AAA1 1001 0011

no

yes

QUERY LAMP POWER ON

148

YAAA AAA1 1001 0100

no

yes

QUERY LIMIT ERROR

149

YAAA AAA1 1001 0101

no

yes

QUERY RESET STATE

150

YAAA AAA1 1001 0110

no

yes

QUERY MISSING SHORT ADDRESS

151

YAAA AAA1 1001 0111

no

yes

QUERY VERSION NUMBER

152

YAAA AAA1 1001 1000

no

yes

QUERY CONTENT DT